TM3DQ8R
Módulo TM3 – Relés de 8 salidas ((*)), marca Schneider E.
Characteristics
range of product |
Modicon TM3
|
product or component type |
Discrete output module
|
range compatibility |
Modicon M241
Modicon M221 Modicon M251 |
discrete output type |
Relay normally open
|
discrete output number |
8
|
discrete output logic |
Positive or negative
|
discrete output voltage |
24 V DC relay output
240 V AC |
discrete output current |
2000 mA relay output
|
discrete I/O number |
8
|
current consumption |
5 mAat 5 V DC via bus connector at state off
0 mAat 24 V DC via bus connector at state off 40 mAat 24 V DC via bus connector at state on 30 mAat 5 V DC via bus connector at state on |
response time |
10 ms turn-on
5 ms turn-off |
mechanical durability |
20000000 cycles
|
minimum load |
10 mA at 5 V DC relay output
|
local signalling |
1 LED per channel greenfor output status
|
electrical connection |
Removable screw terminal block pitch 5.08 mm with 11 terminal(s) of 2.5 mm² connection capacity for outputs
|
max cable distance between devices |
Unshielded cable: 30 m for relay output
|
insulation |
2300 V AC between output and internal logic
750 V AC between outputs 1500 V AC between output groups |
marking |
CE
|
mounting support |
Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715 Plate or panel with fixing kit |
height |
3.54 in (90 mm)
|
depth |
3.33 in (84.6 mm)
|
width |
27.4 mm
|
product weight |
0.24 lb(US) (0.11 kg)
|
standards |
EN/IEC 61010-2-201
EN/IEC 61131-2 |
product certifications |
cULus
C-Tick |
resistance to electrostatic discharge |
4 kV (on contact) conforming to EN/IEC 61000-4-2
8 kV (in air) conforming to EN/IEC 61000-4-2 |
resistance to electromagnetic fields |
9.14 V/yd (10 V/m) at 80 MHz…1 GHz conforming to EN/IEC 61000-4-3
2.74 V/yd (3 V/m) at 1.4 GHz…2 GHz conforming to EN/IEC 61000-4-3 0.91 V/yd (1 V/m) at 2 GHz…3 GHz conforming to EN/IEC 61000-4-3 |
resistance to magnetic fields |
30 A/m conforming to EN/IEC 61000-4-8
|
resistance to fast transients |
2 kV relay output conforming to EN/IEC 61000-4-4
|
surge withstand |
1 kV I/O (DC) in common mode conforming to EN/IEC 61000-4-5
|
resistance to conducted disturbances |
10 Vrmsat 0.15…80 MHz conforming to EN/IEC 61000-4-6
3 Vrmsat spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL) |
electromagnetic emission |
Radiated emissions, test level: 40 dBμV/m QP with class A, condition of test: 10 m (radio frequency: 30…230 MHz) conforming to EN/IEC 55011
Radiated emissions, test level: 47 dBμV/m QP with class A, condition of test: 10 m (radio frequency: 230 MHz…1 GHz) conforming to EN/IEC 55011 |
ambient air temperature for operation |
14…131 °F (-10…55 °C) horizontal installation
-10…35 °C vertical installation |
ambient air temperature for storage |
-13…158 °F (-25…70 °C)
|
relative humidity |
10…95 % without condensation in operation
10…95 % without condensation in storage |
IP degree of protection |
IP20 with protective cover in place
|
pollution degree |
2
|
operating altitude |
0…6561.68 ft (0…2000 m)
|
storage altitude |
0…9842.52 ft (0…3000 m)
|
vibration resistance |
3.5 mm (vibration frequency: 5…8.4 Hz) on DIN rail
3 gn (vibration frequency: 8.4…150 Hz) on DIN rail 3.5 mm (vibration frequency: 5…8.4 Hz) on panel 3 gn (vibration frequency: 8.4…150 Hz) on panel |
shock resistance |
15 gn (test wave duration:11 ms)
|
Valoraciones